1. Home
  2. Terminology, definitions and tables
  3. Minimum distances for work procedures

Minimum distances for work procedures

Minimum distances for live working zone and vicinity zone

Nominal system voltage
Root mean squared

UN kV
Live working zone
Distance in air from bare live part to outer boundary of live zone

DL mm
Vicinity zone
Distance in air from bare live part to outer boundary of live zone

DV mm
≤ 1No contact300
3 601120
3 901120
10 1201150
151601160
202201220
303201320
363801380
40*4301430
454801480
50*5301530
606301630
707501630
11010002000
13211003000
15012003000
22016003000
27519004000
38025004000
400*27004300
48032006100
70053008400
*Linearly extrapolated from the voltages in the corresponding table in EN-50110-1